{"product_id":"burnham-boiler-103310-01","title":"Burnham Boiler 103310-01 Flame Sensor","description":"\u003cp\u003eThe \u003cstrong\u003eBurnham Boiler 103310-01 Flame Sensor Kit\u003c\/strong\u003e is the \u003cstrong\u003eOEM\u003c\/strong\u003e replacement \u003cstrong\u003eflame sensor\u003c\/strong\u003e and \u003cstrong\u003egasket\u003c\/strong\u003e kit from \u003cstrong\u003eBurnham\u003c\/strong\u003e. The \u003cstrong\u003eflame sensor\u003c\/strong\u003e is the safety part that proves the burner is actually lit. It sits in the \u003cstrong\u003eflame\u003c\/strong\u003e and carries a tiny current that the \u003cstrong\u003eignition control\u003c\/strong\u003e reads through \u003cstrong\u003eflame rectification\u003c\/strong\u003e, and as long as that signal is present the control keeps the gas valve open. If the signal disappears, the control shuts the gas off within seconds, which is exactly what you want when the \u003cstrong\u003eflame\u003c\/strong\u003e goes out.\u003c\/p\u003e\n\n\u003cp\u003eOver time the sensing rod becomes coated with oxide and combustion residue the tip erodes, or the \u003cstrong\u003egasket\u003c\/strong\u003e at the mounting hardens in the heat, and the symptoms follow a pattern: a boiler that lights and then shuts down after a few seconds, a \u003cstrong\u003eflame failure\u003c\/strong\u003e fault, an \u003cstrong\u003eignition lockout\u003c\/strong\u003e that clears for a day and then comes back, or a weak \u003cstrong\u003eflame signal\u003c\/strong\u003e on the control display. Cleaning the rod buys a little time, but a pitted or badly eroded rod calls for replacement, and the kit supplies a new sensor with a new \u003cstrong\u003egasket\u003c\/strong\u003e so the mounting is resealed at the same time. Burnham uses more than one flame sensor kit number across its boiler families. The \u003cstrong\u003e103339-01\u003c\/strong\u003e and the \u003cstrong\u003e105798-01\u003c\/strong\u003e are separate \u003cstrong\u003eBurnham\u003c\/strong\u003e flame sensor kits, and this \u003cstrong\u003e103310-01\u003c\/strong\u003e is another, so the number decides the match rather than the look of the part.\u003c\/p\u003e\n\n\u003cp\u003eTo replace it, switch off the power and the gas and let the boiler cool. Disconnect the lead from the sensor, remove the old \u003cstrong\u003esensor\u003c\/strong\u003e from its mounting and clean off the old \u003cstrong\u003egasket\u003c\/strong\u003e. Fit the new sensor with the new gasket, reconnect the lead, restore power and gas and watch a complete start sequence. Check that the \u003cstrong\u003eflame signal\u003c\/strong\u003e on the control is steady, the \u003cstrong\u003eflame\u003c\/strong\u003e is stable and \u003cstrong\u003ecombustion\u003c\/strong\u003e is within range. Keep the sensing rod clear of the burner surface and away from anything that could ground it. Match the kit number to the original part and confirm the boiler model on the rating plate before ordering, since the same sensor is not used on every \u003cstrong\u003eBurnham\u003c\/strong\u003e boiler.\u003c\/p\u003e\n\n\u003cp\u003e\u003cstrong\u003eKey Benefits\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n    \u003cli\u003e\n\u003cstrong\u003eSensor And Gasket:\u003c\/strong\u003e A new \u003cstrong\u003eflame sensor\u003c\/strong\u003e and \u003cstrong\u003egasket\u003c\/strong\u003e in one kit, so the mounting is resealed with the new sensor.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eRestores Flame Proving:\u003c\/strong\u003e A clean, healthy \u003cstrong\u003eflame sensor\u003c\/strong\u003e ends \u003cstrong\u003eflame failure\u003c\/strong\u003e faults and \u003cstrong\u003eignition lockouts\u003c\/strong\u003e caused by a weak \u003cstrong\u003eflame signal\u003c\/strong\u003e.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eOEM Burnham Kit:\u003c\/strong\u003e The \u003cstrong\u003e103310-01\u003c\/strong\u003e is the \u003cstrong\u003eBurnham\u003c\/strong\u003e factory \u003cstrong\u003eflame sensor\u003c\/strong\u003e kit, not a generic rod.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eNumber Decides The Match:\u003c\/strong\u003e Related kits such as the \u003cstrong\u003e103339-01\u003c\/strong\u003e and \u003cstrong\u003e105798-01\u003c\/strong\u003e are separate part numbers, so verify before ordering.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003cp\u003e\u003cstrong\u003eCommon Questions\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n    \u003cli\u003e\n\u003cstrong\u003eWhat does a flame sensor do?\u003c\/strong\u003e It proves the \u003cstrong\u003eflame\u003c\/strong\u003e is present by carrying a small current that the \u003cstrong\u003eignition control\u003c\/strong\u003e reads through \u003cstrong\u003eflame rectification\u003c\/strong\u003e.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eWhat are the signs of a failing sensor?\u003c\/strong\u003e The boiler lights and shuts down, shows a \u003cstrong\u003eflame failure\u003c\/strong\u003e fault, or the \u003cstrong\u003eflame signal\u003c\/strong\u003e reads weak.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eIs it the same as the 103339-01 or 105798-01?\u003c\/strong\u003e No. They are separate \u003cstrong\u003eBurnham\u003c\/strong\u003e kit numbers, so match the number to the original part.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003cp\u003eDisclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.\u003c\/p\u003e","brand":"Burnham Boiler","offers":[{"title":"Default Title","offer_id":68120328405170,"sku":"103310-01","price":165.0,"currency_code":"CAD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1838\/2375\/files\/ac-parts-1000x1000_d8f6c0df-eeb5-4a7f-8ee2-4f92681ea310.webp?v=1755632728","url":"https:\/\/www.gsistore.com\/en-ca\/products\/burnham-boiler-103310-01","provider":"GSIstore","version":"1.0","type":"link"}