{"product_id":"burnham-boiler-108847-01","title":"Burnham 108847-01 Limit Control","description":"\u003cp\u003eThe \u003cstrong\u003eBurnham 108847-01 High Limit Temperature Control\u003c\/strong\u003e is an OEM \u003cstrong\u003emanual reset high limit\u003c\/strong\u003e with a \u003cstrong\u003e210°F\u003c\/strong\u003e trip point for \u003cstrong\u003eBurnham hot water boilers\u003c\/strong\u003e. Its job is simple and critical: if the boiler water climbs to \u003cstrong\u003e210°F\u003c\/strong\u003e, the control opens its contacts, cuts the \u003cstrong\u003eburner circuit\u003c\/strong\u003e and locks the boiler out. Unlike an automatic reset limit, a \u003cstrong\u003emanual reset\u003c\/strong\u003e control stays open until someone presses the red \u003cstrong\u003ereset button\u003c\/strong\u003e on the case, which forces a technician to find out why the boiler overheated before it fires again. The control is a gray enclosure with a \u003cstrong\u003eResideo\u003c\/strong\u003e label and a red push button marked to reset the switch.\u003c\/p\u003e\n\n\u003cp\u003eThe \u003cstrong\u003ehigh limit\u003c\/strong\u003e is the safety backstop behind the boiler's operating control. The operating \u003cstrong\u003eaquastat\u003c\/strong\u003e cycles the burner at the normal set point, and the \u003cstrong\u003e108847-01\u003c\/strong\u003e only acts when something has gone wrong and the water temperature has run past that point. That makes the trip point important: a \u003cstrong\u003e210°F\u003c\/strong\u003e control is not interchangeable with a lower-temperature limit such as the \u003cstrong\u003e6016066\u003c\/strong\u003e, a \u003cstrong\u003eBurnham\u003c\/strong\u003e \u003cstrong\u003emanual reset\u003c\/strong\u003e limit switch that opens at \u003cstrong\u003e200°F\u003c\/strong\u003e. Always match the replacement's temperature and reset type to the original, and never jumper, bypass or raise a limit to stop a nuisance trip. The \u003cstrong\u003e108847-01\u003c\/strong\u003e is a safety limit, not a substitute for the operating control.\u003c\/p\u003e\n\n\u003cp\u003eWhen a high limit trips, the reset button is the symptom, not the cause. Common causes include no flow from a failed \u003cstrong\u003ecirculator\u003c\/strong\u003e or a closed \u003cstrong\u003ezone valve\u003c\/strong\u003e, an air-bound loop, a scaled or dirty heat exchanger, an operating \u003cstrong\u003eaquastat\u003c\/strong\u003e that failed and let the water run hot, or a limit that has drifted and trips early. Check flow and the operating control first, reset the limit once the cause is corrected, and watch the boiler through a complete heating cycle. If the limit trips repeatedly with confirmed good flow and a verified boiler temperature, or will not reset after the boiler has cooled, the control itself has failed and the \u003cstrong\u003e108847-01\u003c\/strong\u003e should be replaced. Shut off the power before opening the control enclosure, and match the replacement to the boiler by model and serial number.\u003c\/p\u003e\n\n\u003cp\u003e\u003cstrong\u003eKey Benefits\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n    \u003cli\u003e\n\u003cstrong\u003eManual Reset Safety:\u003c\/strong\u003e Locks the \u003cstrong\u003eburner circuit\u003c\/strong\u003e open after an overtemperature event until a technician presses the \u003cstrong\u003ereset button\u003c\/strong\u003e.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003e210°F Trip Point:\u003c\/strong\u003e A fixed \u003cstrong\u003e210°F\u003c\/strong\u003e high limit set point, matched to the original \u003cstrong\u003eBurnham\u003c\/strong\u003e control.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eResideo Control:\u003c\/strong\u003e An OEM \u003cstrong\u003eResideo\u003c\/strong\u003e control built for \u003cstrong\u003ehot water boiler\u003c\/strong\u003e limit duty.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eClear Reset Button:\u003c\/strong\u003e The red \u003cstrong\u003epush button\u003c\/strong\u003e is marked for reset and is easy to find on the front of the case.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003cp\u003e\u003cstrong\u003eCommon Questions\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n    \u003cli\u003e\n\u003cstrong\u003eWhat temperature does the 108847-01 trip at?\u003c\/strong\u003e \u003cstrong\u003e210°F\u003c\/strong\u003e. The \u003cstrong\u003e6016066\u003c\/strong\u003e is a \u003cstrong\u003e200°F\u003c\/strong\u003e \u003cstrong\u003emanual reset\u003c\/strong\u003e limit, so the two are not interchangeable.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eWhat does manual reset mean?\u003c\/strong\u003e After the control trips on high temperature, the \u003cstrong\u003eburner circuit\u003c\/strong\u003e stays open until the red \u003cstrong\u003ereset button\u003c\/strong\u003e is pressed, even after the boiler water cools.\u003c\/li\u003e\n    \u003cli\u003e\n\u003cstrong\u003eCan it be used as the operating aquastat?\u003c\/strong\u003e No. The \u003cstrong\u003e108847-01\u003c\/strong\u003e is a \u003cstrong\u003ehigh limit\u003c\/strong\u003e safety control. The boiler's operating \u003cstrong\u003eaquastat\u003c\/strong\u003e or control still sets the normal water temperature.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003cp\u003eDisclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.\u003c\/p\u003e","brand":"Burnham Boiler","offers":[{"title":"Default Title","offer_id":68096124289202,"sku":"108847-01","price":257.0,"currency_code":"CAD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1838\/2375\/files\/108847-01.jpg?v=1795112892","url":"https:\/\/www.gsistore.com\/en-ca\/products\/burnham-boiler-108847-01","provider":"GSIstore","version":"1.0","type":"link"}