Lennox 87268 Motor

Lennox 87268 Motor

Lennox

  • $442.00


The Lennox 87268 is a heavy-duty, 1/4 HP condenser fan motor engineered for direct replacement in commercial and industrial Lennox HVAC units. Operating at 460V on a single-phase 60Hz circuit, this 1075 RPM motor features a standard 48-frame diameter (5.63 inches) to ensure a precise fit in existing brackets. This permanent split capacitor (PSC) motor is designed for high-static pressure environments, utilizing an open air over (OAO) enclosure to facilitate efficient thermal dissipation during continuous operation. With an all-angle mounting capability and an automatic thermal overload protection system, the 87268 manages core temperatures effectively under high ambient conditions. Contractors should verify capacitor requirements, as this replacement condenser motor typically requires a 5 MFD / 370V run capacitor to achieve optimal torque and efficiency ratings required for original equipment performance specification alignment.

Key Benefits for Technicians:
  • OEM Compatibility: Specifically designed to match Lennox HVAC replacement parts specifications, eliminating the need for field modifications.
  • High-Voltage Performance: Optimized for 460V 3-phase systems (utilizing single-phase motor leads) common in commercial refrigeration and rooftop units.
  • Standardized Frame: Features a NEMA 48 frame for easy integration with standard belly bands or stud mounts.
  • Thermal Resilience: OAO design allows the refrigerant-cooled airflow to maintain low winding temperatures, extending the service life of the condenser fan motor 1/4 HP.
Common Industrial Questions:

What is the rotation direction for the 87268?
This motor is typically CWLE (Clockwise Lead End), but technicians should verify the specific fan blade pitch to ensure proper airflow across the condenser coils.

Can I use a 230V capacitor with this motor?
No. Because this is a 460V motor, you must use a capacitor rated for at least 370V or 440V to prevent dielectric breakdown and premature motor failure.

Is this motor suitable for belt-drive applications?
No, the 87268 is a direct-drive HVAC blower motor equivalent designed for fan-on-shaft applications in outdoor condenser sections.

This item is not eligible for free shipping.

Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.