Ranco O20-7041 Control
The Ranco O20-7041 Temperature Control is a heavy-duty wide range temperature control engineered for medium to high-temperature commercial refrigeration. Built with a DPST (Double Pole, Single Throw) switch configuration, this open-on-low temperature control is a direct replacement for Johnson Controls A72AA-3 and A72AA-7. It features a broad 0°F to 100°F temperature range and an adjustable differential of 6°F to 20°F, providing precise cycling for walk-in coolers, display cases, and self-contained refrigeration units. The assembly includes a 96-inch capillary and a 3/8" x 6" cross ambient sensing bulb, ensuring accurate thermal response regardless of the ambient temperature surrounding the NEMA 1 non-conductive enclosure. Designed for the field technician, it utilizes laser-welded bellows and raised screw terminals for efficient wiring and long-term reliability in demanding environments.
Technical Benefits for Contractors:
- Universal Compatibility: Serves as a versatile HVACR service replacement for multiple OEM and Johnson Controls A72 series models.
- Precision Calibration: Features a high-accuracy 7-revolution range adjustment screw for fine-tuning setpoints.
- Electrical Capacity: Rated for heavy-duty switching, handling high-amp loads in commercial refrigeration controls without external relays in many applications.
- Durable Construction: The Ranco O Series design utilizes a steel frame and non-conductive cover to protect internal components from harsh mechanical room conditions.
Common Questions:
Can the Ranco O20-7041 replace a SPST control?
Yes, as a DPST temperature control, it can be wired to replace a Single Pole Single Throw (SPST) unit by utilizing only one set of contacts, providing extra flexibility for your service truck inventory.
What does 'Open-on-Low' mean for this application?
In refrigeration, open-on-low means the switch will break the circuit to the compressor or liquid line solenoid when the temperature drops to the low setpoint, preventing over-cooling or freeze-ups.
How does the cross ambient bulb improve performance?
The cross ambient sensing bulb ensures that the control maintains its calibration even if the capillary or control head is exposed to temperatures warmer or colder than the bulb itself.
This item is not eligible for free shipping.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.
QUESTIONS & ANSWERS
Have a Question?
Be the first to ask a question about this.