Danfoss 060-124166 KP15 Control

Danfoss 060-124166 KP15 Control

Danfoss

  • $224.00


The Danfoss 060-124166 KP15 Control is a professional-grade dual pressure switch engineered for regulating and protecting refrigeration and air conditioning systems. This unit features independent low-pressure (LP) and high-pressure (HP) circuits housed in a rugged, impact-resistant enclosure. Designed for high-reliability applications, it utilizes a snap-action contact system to ensure minimal bounce times, significantly reducing contact wear under heavy electrical loads. The LP side operates within a regulation range of -0.2 to 7.5 bar with an automatic reset, while the HP side covers 8 to 32 bar, also featuring auto-reset functionality. Installation is streamlined via standard 1/4 inch flare connections (1/4 in SAE), making it a direct replacement for many light and heavy commercial condensing units. This SPDT pressure control is vibration and shock resistant, ensuring stable operation in demanding mechanical rooms or outdoor environments where compressor pulsation is a factor.

Key Benefits for HVACR Applications:
  • Dual-Function Protection: Manages both suction and discharge pressure in a single compact housing to prevent compressor slugging or overheating.
  • Enhanced Contact Life: Integrated snap-action mechanism provides rapid switching to mitigate electrical arcing and mechanical fatigue.
  • Precise Field Calibration: Dual scales allow for accurate manual adjustment of cut-in and cut-out set points to match specific system requirements.
  • Robust Environmental Resistance: Fully welded bellows and a corrosion-resistant casing provide long-term durability in high-vibration commercial settings.
  • Universal Compatibility: Standard 1/4 in flare fittings and a versatile SPDT contact logic facilitate integration into various control circuits and alarm systems.
Common Technician Questions:

What is the difference between the 060-124166 and other KP15 models?
This specific model features automatic reset on both the high and low-pressure sides. Other variations may include manual reset options for high-pressure safety compliance which requires a technician to physically inspect the system before restarting.

How do I set the differential on the low-pressure side?
The LP differential index is adjustable between 0.7 and 4.0 bar. Use the adjustment screws on the top of the unit while referencing the internal scale, though final verification with a calibrated manifold gauge set is recommended during commissioning.

Can this be used with R-410A systems?
Yes, the 32 bar (464 psi) high-pressure limit is compatible with many R-410A high-side safety requirements, though always verify your specific system's design pressure before installation.