Carrier 312926-256 Pressure Switch

Carrier 312926-256 Pressure Switch

Carrier

  • $80.00


The Carrier 312926-256 Low Pressure Switch is a refrigerant circuit safety switch carrying 240 VAC and 408 PSI ratings. A low pressure switch watches the system and opens its contacts when refrigerant pressure falls below its setting, taking the compressor out of service before it can run starved of refrigerant and cooling. That protects against overheating, poor lubrication and the kind of damage that turns a leak or an airflow problem into a compressor replacement. On a service call, an open switch is a warning to investigate rather than a part to bypass.

This switch has a compact round body with a short copper stub tube for connection to the refrigerant circuit and long insulated leads in yellow and yellow with pink, finished with a white connector. A stub style connection is brazed into place, so the installation calls for proper refrigerant handling and careful heat control. The cut in and cut out settings determine how the switch behaves, and they matter as much as the electrical rating. Read the label on the switch being replaced and compare every value, the connection style and the lead arrangement before you order or install.

Diagnose the circuit before replacing anything. Connect gauges and compare actual pressure with the switch settings. Look for low charge from a leak, a dirty filter, a failed indoor blower, a restricted metering device or very low operating temperatures. Check continuity with the leads isolated. If the switch is open at a pressure where it should be closed, replacement is justified. Recover refrigerant as required, protect the new switch body with a heat sink or wet rag while brazing, purge with nitrogen, then pressure test, evacuate and recharge to the equipment specification. Finish by verifying operation and securing the leads away from hot lines and sharp edges.

Key Benefits

  • Compressor Protection: Opening on low pressure helps stop the compressor before it suffers from poor cooling and lubrication.
  • Stated Ratings: The part carries 240 VAC and 408 PSI figures that you can compare against the original equipment requirements.
  • Brazed Copper Connection: A short copper tube provides a permanent, tight joint in the refrigerant circuit when installed with proper technique.
  • Prewired Leads: Long color coded leads with a connector make it easier to route the switch to the control wiring without adding splices.

Common Questions

  • Can I jumper this switch to get cooling back? Only as a momentary test by a qualified technician, never as a repair. Running without protection can destroy the compressor.
  • What should I match before ordering? Confirm 312926-256 against your unit parts information and compare the pressure settings, electrical rating, connection style and leads with the original switch.
  • Why does the low pressure switch keep opening? Low refrigerant charge, restricted airflow, a plugged filter drier or metering device and cold ambient operation are frequent causes. Fix the underlying condition before judging the switch.