Copeland ZP61K5E-TFD-130 Compressor

Copeland ZP61K5E-TFD-130 Compressor

Copeland

  • $2,670.00


The Copeland ZP61K5E-TFD-130 Scroll Compressor is a fixed-speed Copeland Scroll compressor built for R-410A air-conditioning service. It sits in the 61,500 BTU/hr capacity class, roughly 5 tons, at the AHRI rating point. The TFD electrical code means 460V, 3-phase, 60 Hz power. Published Copeland data lists a rated load amp (RLA) of 9.1 amps, a locked rotor amp (LRA) of 66.1 amps and a maximum continuous current (MCC) of 12.8 amps. The suction connection is 7/8 inch, and the shell is about 6.5 inches in diameter and 17 inches tall. It uses POE (polyol ester) oil, as R-410A compressors do.

The scroll design compresses refrigerant between two interleaved spirals, one fixed and one orbiting, which means fewer moving parts than a reciprocating compressor and smooth, quiet operation. The 130 dash number identifies a specific factory configuration, and Copeland also offers this family in an 800 bill-of-material service option that includes a 42-inch molded plug wiring harness, mounting parts and instructions. For that reason, match the complete ZP61K5E-TFD-130 model number, not just the ZP61K5E platform, and check terminal and plug arrangement before ordering. Copeland now identifies its LXE platform as the service replacement for earlier ZP K5, K6 and K7 R-410A compressors across all voltages including TFD, so confirm the current replacement model if this exact number is no longer supplied.

A three-phase scroll compresses in only one direction, so phase rotation matters. A compressor that runs with a loud, harsh sound, draws low current and fails to build head pressure is usually turning backward, and the fix is swapping two power leads. Before installing any replacement, find out why the original failed. After a motor burnout, clean the system and install a new liquid line filter-drier. Pull a deep vacuum, weigh in the nameplate charge with a scale, and check the contactor, supply voltage and phase balance. Compressors that fail from flooded starts, low airflow or voltage imbalance will fail again if the cause is left in place.

Key Benefits

  • Correct Rating: 61,500 BTU/hr class R-410A scroll on 460V, 3-phase, 60 Hz power with 9.1 RLA and 66.1 LRA.
  • Scroll Efficiency: fixed-speed Copeland Scroll design with smooth compression and low sound for residential and commercial air-conditioning.
  • Defined Connections: 7/8 inch suction connection and compact 6.5 x 17 inch shell help confirm fit against the failed compressor.
  • Current Platform Path: LXE is Copeland's service platform for ZP K5/K6/K7 compressors, which helps when the original number has changed.

Common Questions

  • What refrigerant and voltage does the ZP61K5E-TFD-130 use? It is an R-410A compressor on 460V, 3-phase, 60 Hz power. The TFD code is the three-phase 460V configuration.
  • Is this a 5-ton compressor? It is in the 5-ton class, rated at 61,500 BTU/hr by Copeland. Actual capacity changes with evaporating and condensing conditions, so do not choose a replacement by BTU alone.
  • Can I replace it with another Copeland model? Only after verifying refrigerant, voltage and phase, connections, mounting and electrical connection style. Compare the ZP61K5E-TFD-130, the 800 bill-of-material version and the current LXE model against the original compressor and equipment data.

Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.

This item is not eligible for free shipping and must be shipped via trucking. Please contact us for a freight quote.