Raypak 009057F Control
When you are troubleshooting a mid-efficiency boiler or commercial water heater and find a failed ignition sequence, the Raypak 009057F Control is the specific field replacement you need for systems utilizing a 120V Hot Surface Ignition (HSI). This integrated Raypak ignition module manages the gas valve and igniter sequence with precision, featuring a strict 4-second Trial for Ignition (TFI) window. Engineered for single-try ignition logic, this board requires a manual reset if a flame is not sensed, preventing unsafe gas accumulation in the combustion chamber. As a veteran-grade HVACR replacement part, it provides reliable flame rectification and direct compatibility with Raypak Hi Delta and Raytherm atmospheric platforms. The rugged solid-state construction ensures steady performance in high-demand mechanical rooms, serving as a direct cross-reference for the Raypak 62YC31 ignition control.
Key Benefits for the Contractor- Precise 120V HSI Timing: The 4-second TFI ensures a narrow, safe window for flame establishment, protecting the heat exchanger.
- Safety-First Manual Reset: Requires technician intervention after a lockout, ensuring the root cause of ignition failure is addressed.
- OEM Compatibility: Designed specifically for Raypak pool heater parts and commercial boiler lineups to ensure proper pin-to-pin alignment.
- Robust Flame Sensing: Utilizes advanced flame rectification circuits to maintain stable operation even with marginal grounding.
- Simplified Troubleshooting: The 009057F manual reset kit allows for clear diagnostic feedback during the startup sequence.
What causes a lockout on the 009057F ignition module?
A lockout typically occurs if the 120V HSI fails to reach the proper temperature or if the flame sensor does not detect a microamp signal within the 4-second TFI. Common field issues include cracked igniters, poor grounding, or restricted gas pressure.
Is the Raypak 009057F compatible with 24V ignition systems?
No, this specific control is strictly for 120V HSI ignition control systems. Applying 24V to this board or using it in a 24V circuit will cause immediate component failure and poses a safety risk.
Can I bypass the manual reset on this control?
The manual reset is a critical safety feature of the Raypak 009057F Control and cannot be bypassed. If the unit continues to trip, technicians should inspect the burner tray for proper alignment and clean the flame probe.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.
QUESTIONS & ANSWERS
Have a Question?
Be the first to ask a question about this.