Veris Industries PWXX05S Transducer
The Veris Industries PWXX05S is a high-performance wet media differential pressure transducer designed for precise monitoring in demanding HVACR environments. Engineered for versatility, this 0-250 psi pressure sensor utilizes microprocessor-profiled sensors to maintain high accuracy and stability when measuring pressure drops across pumps, heat exchangers, and filters. The PWXX05S features a 4-20mA analog output (also field-selectable for 0-5V or 0-10V) and a rugged NEMA 4 die-cast enclosure, making it suitable for both plant rooms and outdoor installations. A critical advantage for field technicians is the jumper-selectable port swap feature, which allows you to correct piping errors electronically without the need for physical replumbing. This unit is built to handle non-corrosive liquids and gases, ensuring reliable chiller/boiler differential pressure control with electronic surge dampening to prevent signal noise from system turbulence.
Key Benefits for the Contractor- Field-Adjustable Flexibility: Includes four switch-selectable pressure ranges (25, 50, 125, and 250 PSID), reducing the need to stock multiple dedicated models.
- Simplified Commissioning: Features a pushbutton auto-zero and a remote zero-input terminal to facilitate rapid field calibration.
- Robust Overpressure Protection: Designed to withstand 2x full-scale proof pressure and 5x full-scale burst pressure, protecting the 17-4 PH stainless steel sensor from common system spikes.
- Status Diagnostics: Integrated dual-color LED provides immediate visual feedback for normal operation, overpressure, or reversed port conditions.
Can I use this sensor with domestic water systems?
Yes, the PWXX05S utilizes 17-4 PH stainless steel wetted parts, making it compatible with water and other non-corrosive wet media typically found in commercial HVAC loops.
What happens if I accidentally plumb the high and low ports backward?
You do not need to cut and re-sweat the lines. Simply locate the internal port swap jumper and move it to the swap position to invert the sensor logic electronically.
Does this unit support 2-wire or 3-wire configurations?
The Veris PWXX05S is a 3-wire wet/wet transducer when configured for voltage output or standard mA loops. Always ensure your power supply meets the 12-30VDC or 24VAC requirement for proper excitation.