Danfoss 060-5247 Pressure Control
The Danfoss 060-5247 Pressure Control is a professional-grade KPU15 dual pressure switch engineered for high-demand HVAC and refrigeration service. This unit features an automatic reset on both the high and low-pressure sides, providing reliable system protection without the need for manual intervention after a trip. The low-pressure side operates within a range of -6 inHg to 108 psig, while the high-pressure side is rated for 100 to 465 psig. Designed as a direct drop-in replacement for the O12-1505 and 060-524700, it utilizes a 1/4" male flare connection (DIN 8906) for straightforward integration into existing liquid or suction lines. With a heavy-duty SPDT contact function (NO+NC) and an IP30 rated enclosure, this control manages FLA 24 A at 120 V AC, making it suitable for cycling compressors or signaling alarms in commercial cooling applications.
Key Benefits for Technicians:- Broad Refrigerant Compatibility: Optimized for use with R134a, R22, R404A, R407 series, R513A, and other non-corrosive, oil-free refrigerants.
- High Electrical Capacity: Rugged 24A electrical rating allows for direct control of many single-phase motors without an intermediate contactor.
- Dual-Function Protection: Combined high/low monitoring reduces the number of components in the circuit, simplifying troubleshooting and installation.
- Precise Differentials: Adjustable low-side differential (10–60 psi) and a fixed 60 psi high-side differential ensure stable system cycling and prevent short-cycling.
Is the Danfoss 060-5247 compatible with R410A systems?
No, this specific KPU15 model is rated for a maximum working pressure of 465 psig on the high side. For R410A systems requiring higher burst protection, a high-pressure specific control should be used.
What is the difference between KPU and KP series?
The KPU series, including the 060-5247, is specifically tailored for the North American market, meeting cULus and UL873 standards with terminal markings familiar to local contractors.
Does this unit require a manual reset?
This model is an automatic reset dual pressure switch. Once the system pressure returns to the differential setpoint, the contacts will automatically re-close to resume operation.