Watts 0391007 Backflow Preventer
The Watts 0391007 009M2QT 2" Backflow Preventer is a professional-grade reduced pressure zone assembly designed to protect potable water supplies by preventing backsiphonage and backpressure in high-hazard applications. This unit serves as the direct replacement and update for the legacy Watts 0063010, featuring a compact, bronze body construction that simplifies installation in tight mechanical rooms. The Watts 009 Series utilizes a modular design with two independent check valves and a pressure differential relief valve located between them. This 2 inch RPZ valve is rated for working pressures up to 175 psi and fluid temperatures from 33°F to 180°F. Contractors prioritize this model for its 009M2QT lead free compliance and the inclusion of two full-port, resilient seated threaded quarter-turn ball valve shutoffs. The single cover design and replaceable seats ensure streamlined field maintenance and testing without removing the assembly from the line.
Key Benefits
- Enhanced Protection: Provides superior protection against backflow in high-hazard cross-connections.
- Compact Footprint: The modular reduced pressure principle assembly design allows for easy retrofitting in existing piping configurations.
- Field Serviceability: Features a single access cover and replaceable check seats for rapid technician maintenance.
- Durable Construction: Built with a corrosion-resistant bronze body and stainless steel internal parts for long-term reliability.
- Legacy Replacement: Fully compatible update for the 0063010 model, ensuring seamless mechanical alignment.
Common Questions
How do I troubleshoot a constantly leaking relief valve?
Usually, a discharge from the relief valve indicates either dirt/debris on the first check valve seat or a significant pressure drop in the supply line. Inspect the first check assembly for fouling before replacing internal components.
Is the 009M2QT suitable for vertical installation?
Yes, the Watts 0391007 is designed for both horizontal and vertical "up" flow orientations, provided the relief valve remains accessible for testing and drainage.
Does this unit meet current lead-free regulations?
This specific potable water backflow preventer is manufactured to meet all current Lead Free requirements for plumbing applications in high-hazard environments.
This item is not eligible for free shipping.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.
QUESTIONS & ANSWERS
Have a Question?
Be the first to ask a question about this.