Johnson Controls V46AB-1 Regulating Valve

Johnson Controls V46AB-1 Regulating Valve

Johnson Controls

  • $218.67


The Johnson Controls V46AB-1 Regulating Valve is a direct acting pressure actuated water regulating valve specifically engineered for maintaining refrigerant head pressure control in systems using non-corrosive refrigerants. This 1/2" NPT commercial water valve features a cast brass body and a robust pressure-balanced design, ensuring stable performance despite fluctuations in water pressure. For the technician in the field, the V46AB-1 provides a reliable opening point range of 70 to 260 PSI, making it ideal for water-cooled condenser applications in ice machines, computer room air conditioning units, and refrigeration cases. It comes equipped with a 30-inch capillary and a 1/4" flare nut (Style 45) pressure element for straightforward integration. This unit serves as the direct replacement for V46AB-22 and V46AB-17; simply cut the flare to adapt to a style 34 connection when replacing older V46AB-17 models. The take-apart construction allows for full interior access without pumping down the system.

  • Direct Acting Operation: Valve opens on pressure rise to effectively modulate flow through the condenser.
  • Broad Compatibility: Designed for use with standard, non-corrosive refrigerants and systems utilizing water or glycol.
  • Enhanced Serviceability: Features an accessible range spring for manual flushing and a take-apart design for easy maintenance.
  • Durable Construction: Cast brass body and corrosion-resistant internal components extend service life in demanding commercial environments.
  • Standardized Connections: 1/2" NPT water connections and Style 45 pressure connections simplify the installation process.
Common Questions:
  • How do I adjust the opening point on the V46AB-1? Use the range adjustment screw to set the opening point within the 70 to 260 PSI range while the system is operating under load.
  • What is the maximum water temperature for this valve? This valve is rated for a maximum water temperature of 170°F (77°C) and a maximum water pressure of 150 PSI.
  • Can I use the V46AB-1 with ammonia systems? No, this commercial brass model is for non-corrosive refrigerants only; ammonia applications require specific maritime or ammonia-rated steel valves.

Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.

QUESTIONS & ANSWERS

Ask a Question
  • by changing the valve will i lose the freeon

    Anytime a system is open up for part change there will be some refrigerant loss most likely. Loss can be prevented or minimized by shutting off the section where the part is located. This has to be observed and performed correctly in the field.