Warrick 27A1D0 1NO & 1NC
The Warrick 27A1D0 is a high-performance intrinsically safe liquid level control designed for demanding industrial environments including Class I, II, and III hazardous locations. This conductivity-based level relay operates on a 120V AC supply and features a factory-set sensitivity of 3K Ohms, ensuring reliable direct acting logic for pump control, sewage systems, and storage tank monitoring. Built with solid-state reliability and integrated surge suppression, the 27A1D0 provides a robust SPDT (1NO/1NC) output rated for 8A resistive at 120/240VAC. Whether configured for single-level service like a high-level alarm or differential service for pump-down applications, this controller maintains precision without the risk of igniting flammable atmospheres. Its compact design facilitates easy mounting within any standard NEMA enclosure or control panel.
Key Benefits- Intrinsically Safe Design: UL and CSA approved for hazardous atmospheres, eliminating the need for bulky explosion-proof housings.
- Direct Acting Operation: Specifically calibrated for direct acting logic where the relay energizes upon liquid contact with the probe.
- Industrial Durability: Solid-state internal components ensure longevity in high-cycle waste treatment and pump control applications.
- Versatile Signaling: Features SPDT contacts (Form-C) to provide both normally open and normally closed signaling from a single unit.
- Field Reliability: Includes internal surge suppression to protect sensitive circuitry from transient voltage spikes common in industrial power grids.
How do I wire the Warrick 27A1D0 for high-level alarm service?
For single-level detection, install a metallic jumper between terminals H and L on the Warrick series 27 board. Connect the probe to terminal L and ensure terminal G is properly grounded to the tank or a reference electrode.
What is the maximum distance I can run probe wiring?
The maximum distance is determined by the capacitance and resistance of the field 14-16 AWG MTW/THHN wire. For 120V models, ensure the total resistance of the probe path does not exceed the 3K Ohm sensitivity of the unit.
Can this controller be used in non-metallic tanks?
Yes. In non-metallic vessels, terminal G must be connected to an additional reference electrode of the same length as the longest sensing probe to complete the conductivity circuit.