Wayne Combustion 64299-001 Ignition Control
The Wayne Combustion 64299-001 Ignition Control (Fenwal 35-630505-037) serves as the direct replacement for 64230-001 modules, engineered to manage gas-fired burners in residential and commercial heating cycles. This 24 VAC automatic ignition controller features a 0-second pre-purge, 45-second inter-purge, and a 90-second trial for ignition, ensuring robust flame supervision for boilers and horizontal furnaces. Built with DETECT-A-FLAME technology, the 64299-001 provides safe-start monitoring and an integrated diagnostic LED for rapid field troubleshooting. The module supports both local and remote flame sensing, making it a versatile HVAC burner control replacement for a wide range of appliances. With a -40°F to 176°F operating range and an NC alarm output, this Fenwal 35-63 series module delivers precise 50/60 Hz performance for high-demand combustion systems. Professionals can rely on the blade terminal layout and standard 4-bolt flange mounting for streamlined retrofitting in the field.
Key Benefits- Universal Compatibility: Serves as the official replacement for 64230-001, simplifying inventory for service technicians.
- Safe Start Logic: Features DETECT-A-FLAME monitoring to ensure no flame is present before the ignition sequence begins.
- Onboard Diagnostics: High-visibility system diagnostic LED reduces downtime by identifying fault codes immediately.
- Flexible Sensing: Supports both local (through spark) and remote flame sensing configurations to fit legacy and modern burner designs.
- Wide Temperature Range: Rated for reliable operation between -40°F and 176°F in demanding mechanical rooms.
Is the 64299-001 compatible with the obsolete 64230-001?
Yes, the 64299-001 is the specified direct replacement for 64230-001, utilizing the same terminal connections and mounting footprint for seamless installation.
What does the LED blink pattern indicate during a lockout?
The diagnostic LED provides specific flash codes to indicate a failed trial for ignition, flame loss, or internal circuit faults, allowing for faster board assessment without a multimeter.
Does this module require a specific flame sensor?
This Wayne Combustion ignition module is designed for flexibility, supporting a single-rod local sense through the high-voltage spark electrode or a separate remote flame rod.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.
QUESTIONS & ANSWERS
Ask a Question-
I have a wayne Ign., control m/n 64395-001 is this the Replacement for thr old unit. Also is the purge time and trial times.
64395-001 is a good number. It has a prepurge and interpurge timing of 30 seconds each. Trial for ignition is 3-4 seconds.
Here is the link of this part:
https://www.gsistore.com/products/wayne-combustion-64395-001-ignition-control -
Will this module fit a Space Ray LTU ?
We will need the model and serial numbers off the unit to check. Thnaks