York 025-29583-000 Pressure Transducer

York 025-29583-000 Pressure Transducer

  • $906.06


The York 025-29583-000 Pressure Transducer is a critical OEM component designed for high-precision suction pressure monitoring across a wide range of chiller platforms, including YVAA and YVFA models. This 200# pressure transducer operates with a standardized 5V DC supply voltage, providing a linear 0.5 to 4.5 VDC output signal that the control board utilizes for real-time system diagnostics and compressor staging. Engineered for the rigors of industrial refrigeration, this sensor features a durable stainless steel construction to resist vibration and moisture-related failure, a common issue in high-ambient chiller applications.

For technicians performing chiller maintenance or troubleshooting sensor failure faults, this Johnson Controls manufactured part ensures accurate refrigerant pressure measurement between 0 and 200 PSI. Its digital design includes updated clamping logic to prevent unregulated voltage spikes from triggering nuisance trips on the control panel. By delivering precise electrical feedback, the York 025-29583-000 maintains optimal superheat control and protects the compressor against low-suction conditions, ensuring peak HVAC system efficiency and operational reliability.

Key Benefits:
  • OEM Precision: Genuine York replacement part calibrated for exact compatibility with York chiller control boards.
  • Enhanced Reliability: Advanced voltage clamping prevents sensor failure faults during extreme temperature fluctuations.
  • High Measurement Range: Supports 0-200 PSI range (200# transducer) for versatile suction and system monitoring.
  • Seamless Integration: Features a standardized 3-pin electrical connector and threaded pressure port for rapid field replacement.
Common Questions:
  • What does a 0.3V or 4.9V reading indicate? Voltages outside the 0.5V to 4.5V range typically indicate a failed pressure transducer or a wiring harness fault.
  • Can this be used for discharge pressure? No, this is a 200 PSI suction transducer; discharge applications typically require a 400# or 650# rated sensor.
  • Is a new wiring harness required? It is recommended to inspect the pins for corrosion; if moisture is present, a new transducer harness should be installed simultaneously.

This item is not eligible for free shipping.

Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.