The Burnham 105758-01 Blower Replacement Kit is the OEM combustion blower kit for the Burnham Alpine condensing hot water boiler in the ALP210 size. It includes the blower, the gasket and the mounting hardware needed to swap the blower assembly, so the repair is done with matched parts instead of a pile of loose components. The blower is the engine of the Alpine's sealed combustion system: it moves combustion air and fuel through the burner, pushes the hot gases through the heat exchanger, drives the exhaust out through the vent, and varies its speed with the firing rate as the boiler follows heating demand. The assembly has a cast aluminum scroll housing with a flanged outlet and an electric motor under a dark protective cover.

Burnham sizes the Alpine blower kits by boiler. The 105756-01 is the kit for the ALP80 and ALP105, the 105757-01 is the kit for the ALP150, and the 105758-01 is the kit for the ALP210. A further blower repair kit, the 104999-01, covers a different Alpine size. Ordering the wrong size is the most common mistake on a blower job, so match the kit to the size on the boiler's rating plate. Other service parts for the same boiler include the 103339-01 flame sensor kit and the 103005-01 igniter kit, both worth replacing at the same visit if the boiler has run for several seasons. The gasket seals the blower to the boiler and should be replaced every time the blower is removed.

A blower on its way out usually announces itself. The control flags a blower or fan speed fault, the boiler fails to prove airflow and locks out before ignition, the fan runs rough or noisy, or the boiler hunts and shuts down when demand is high. Before condemning the blower, confirm that the vent and the combustion air intake are clear, that the condensate trap is draining and not backing up, and that the blower's power and control plugs are fully seated and undamaged. If the blower is the problem, shut off the power and the gas, release the old blower from its mounting, install the new gasket and the 105758-01 blower with the supplied hardware, reconnect the plugs, leak-test the gas connection and run a combustion analysis to confirm the boiler fires cleanly across its range.

Key Benefits

  • Correct Size: The 105758-01 is the blower kit for the ALP210, specified by Burnham for that boiler size.
  • Matched Parts: Blower, gasket and mounting hardware come in one kit, so the joint to the boiler is resealed with the right gasket.
  • Restores Combustion Air: A new blower restores proper combustion air delivery and steady fan speed through the whole firing range.
  • Genuine OEM: A factory Burnham replacement for the Alpine condensing boiler, built to the original blower specification.

Common Questions

  • Which Alpine does the 105758-01 fit? The ALP210. For the ALP80 and ALP105 use the 105756-01, and for the ALP150 use the 105757-01.
  • What comes in the kit? The blower, the gasket and the mounting hardware.
  • Should the flame sensor be replaced at the same time? It is a convenient time if the boiler has symptoms or years of service. The 103339-01 flame sensor kit and the 103005-01 igniter kit are the companion parts.