Carrier FC-3301C20 Electric Heater

Carrier FC-3301C20 Electric Heater

Carrier

  • $297.29


The Carrier FC-3301C20 Electric Heater Kit is a field-installed 20 kW electric heat strip for Carrier air handlers and fan coil units operating on 208/230V, single-phase, 50/60 Hz power. The heat comes from an advanced alloy open coil element bank, which is bare resistance wire stretched across the airstream so the heat moves straight into the air with nothing in between to slow it down. This is a circuit breaker model, so branch-circuit overcurrent protection comes with the kit, along with the primary and secondary limit controls that cut the elements off when airflow drops. The controls are built to tie into the factory control system of the unit, and the construction is ETL listed.

Kilowatt ratings for this class of heater are stated at 240V. Element output falls with the square of the voltage, so on a 208V supply the same heater delivers roughly 15 kW. Plan the supply circuit with that in mind: a 20 kW load pulls roughly 80 amps at 230V, so wire size and overcurrent protection come from the heater data label and the unit's installation instructions, never from guesswork. Carrier's own accessory-heater tables place the 20 kW circuit-breaker heater class, catalog number KFCEH3301C20, in the larger cabinets of the FA, FC, FX and FY fan coil families (sizes 030 through 060), and the same heater class is listed for the FB, FE, FH, FK, FV and PF series. Always confirm the match against the heater table for the exact unit model. The fused version of this size is a separate number, KFCEH3201F20 from Carrier and FC-3201F20 in this FC- series, and the older Carrier number KFAEH0601F20 belongs to the same 20 kW family and still turns up on earlier parts lists.

Installation follows the usual accessory-heater routine. Kill the power at the disconnect, pull the blower access panel, slide the element assembly into the heater opening and secure the control plate. A circuit breaker heater adds a breaker box that mounts on the cabinet, and the low-voltage heater harness plug connects to the unit's wire harness. Follow the installation instructions packed with the kit, then confirm the blower delivers at least the minimum airflow the heater requires. When a unit stops making heat, work from the supply side in: check for a tripped breaker, confirm voltage at the heater relays, then look at the limit controls. A dirty filter or a crushed duct is the usual reason a limit opens. A single dead element reads open when isolated and checked with a meter, and an element that sags and touches the frame will trip the breaker as soon as it is energized.

Key Benefits

  • Built-In Breaker Protection: The circuit breaker assembly gives the heater its own overcurrent protection, and the primary and secondary limit controls back it up when airflow is lost.
  • 20 kW Output: Delivers supplemental or primary electric heat for larger fan coil and air handler cabinets, including systems paired with a heat pump.
  • Open Coil Alloy Elements: Direct contact with the airstream gives quick heat transfer and a simple, easy-to-inspect element layout.
  • Factory Control Compatibility: Ties into the unit's factory control system, ships boxed individually with installation instructions, and an optional single-point power accessory kit is available.

Common Questions

  • Is a single-point power kit required for the FC-3301C20? No. The single-point power accessory kit is optional and consolidates the field power wiring into one connection point from the panel. Without it, the supply is wired as the heater data label and wiring diagram direct.
  • What airflow does a 20 kW heater need? The minimum airflow depends on the heater size and the fan coil or air handler model. Compare the blower's CFM on the speed used for electric heat to the minimum listed for a 20 kW heater in the unit's installation instructions.
  • Does this heater kit include limit controls? Yes. Primary and secondary limit controls open the heater circuit if the air is restricted. A limit that keeps tripping is pointing at an airflow problem, so find the cause instead of bypassing the control.