Fireye EP160 Program Module
The Fireye EP160 Program Module is a critical engineering component for the Flame-Monitor Burner Management Control System, specifically designed for use with E100 and E110 chassis. As a veteran-grade flame safeguard control, the EP160 provides precise start-up programming and continuous flame monitoring supervision. Hard-coded with a 30-second purge cycle and a 10/15-second Trial for Ignition (TFI), this non-recycle module ensures that any failure in the running interlock circuit or a flame failure results in an immediate safety lockout, preventing dangerous fuel accumulation. It is fully backward compatible with the ED500 and interfaces seamlessly with the ED510 display module for real-time diagnostics and history retrieval.
Key Benefits for Contractors:- Enhanced Safety Logic: The non-recycle (NR) function mandates a manual reset following a safety shutdown, ensuring technicians can investigate the root cause before restarting the burner.
- Precise Timing Control: Features a fixed 30s purge time and a dual 10/15s TFI to meet specific industrial burner requirements and local mechanical codes.
- Advanced Diagnostics: Includes an RJ45 connector for direct integration with the Fireye ED510 display, allowing access to lockout history, burner cycles, and total operating hours.
- Robust System Integration: Designed to monitor the 3-P running interlock circuit, including airflow switches and fuel pressure switches, triggering a fuel valve de-energization within 4 seconds of flame failure.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.
QUESTIONS & ANSWERS
Have a Question?
Be the first to ask a question about this.