Fireye YP100 Programmer

Fireye YP100 Programmer

  • $1,171.67


The Fireye YP100 Programmer is a critical microprocessor-based component designed for the Fireye BurnerLogix burner management control system. Engineered for high-stakes industrial and commercial boiler applications, this non-recycle programmer module establishes the operational logic for the entire chassis. It provides keypad selectable parameters that allow technicians to fine-tune the burner sequencing, including modulation control and open damper proving. With a 4-second flame failure response time (FFRT), the YP100 ensures rapid shutdown during a loss of flame signal, prioritizing combustion safety. This plug-in module is a direct replacement for BurnerLogix YB110 or ZB110 series chassis, offering a simplified upgrade path for existing installations. Its internal memory retains historical data and current program status even after a power interruption, allowing for efficient troubleshooting and reduced downtime on the job site. Designed for durability in mechanical rooms, it operates reliably within a wide temperature range between -40°F and 140°F.

Key Benefits for Technicians:

  • Field-Configurable Timing: Keypad menus allow for precise programming of PTFI and MTFI timings without specialized hardware.
  • Enhanced System Logic: Integrates open damper proving and low fire start interlocks to verify safe operating conditions before ignition.
  • Universal Compatibility: The modular plug-in design fits standard BurnerLogix wiring bases, enabling quick swaps during emergency service calls.
  • Advanced Diagnostics: Smart LEDs and RS485 Modbus communications provide real-time operating status and detailed lockout codes.
  • Increased Turndown: The "revert to pilot" feature allows the system to return to the pilot flame instead of cycling off, optimizing boiler efficiency.

Common Contractor Questions:

Is the Fireye YP100 compatible with my existing UV scanner?
Yes, the YP100 functions within the BurnerLogix system, which supports UV, infrared (IR), and flame rod detectors depending on the specific chassis and amplifier installed. If using an IR-based control, an "IR Learn" operation is recommended for optimal signal reliability.

What is the difference between the YP100 and YP102 modules?
The primary difference is the Flame Failure Response Time (FFRT). The YP100 features a 4-second FFRT, while the YP102 is rated for 2 seconds. Always verify the local code requirements and burner manufacturer specifications before selecting a timing module.

Can I change the pre-purge time on the YP100?
Yes, pre-purge timings are among the keypad selectable parameters. Technicians can configure these settings through the alphanumeric display to match specific application requirements.