Honeywell HP970A1009 Pneumatic Humidistat
The Honeywell HP970A1009 pneumatic humidistat is a direct-acting, two-pipe, single-setpoint humidity controller designed for commercial and industrial HVAC pneumatic control systems. Featuring a humidity scale range of 15% to 75% RH and an adjustable throttling range of 3% to 15% RH, this controller supports precise humidity regulation in conditioned spaces.
The Honeywell direct-acting humidistat increases pneumatic branch pressure as relative humidity rises, providing proportional control of compatible pneumatic valves and damper actuators. Its maximum operating pressure of 25 PSI and operating temperature range of 45°F to 125°F accommodate commercial building automation applications.
Designed for vertical or horizontal mounting, the Honeywell HP970A1009 humidity controller provides installation flexibility for existing pneumatic HVAC systems. This two-pipe pneumatic humidistat is suitable for humidification and dehumidification control applications. Before installation, technicians should verify control action, pneumatic supply pressure, tubing connections, humidity setpoint, and throttling range to ensure accurate calibration and reliable system performance.
Technical Specifications
|
Specification |
Details |
|---|---|
|
Manufacturer |
Honeywell |
|
Model Number |
HP970A1009 |
|
Alternate Model Number |
HP970A1009/U |
|
Series |
HP970 |
|
Product Type |
Pneumatic humidistat |
|
Control Action |
Direct acting (DA) |
|
Control Type |
Proportional |
|
Number of Pipes |
2 |
|
Setpoint |
Single |
|
Humidity Scale Range |
15% to 75% RH |
|
Setpoint Adjustment |
5% RH increments |
|
Throttling Range |
Adjustable, 3% to 15% RH |
|
Maximum Operating Pressure |
25 PSI |
|
Branch Line Pressure Range |
3 to 15 PSI |
|
Operating Temperature Range |
45°F to 125°F (7°C to 52°C) |
|
Storage Temperature Range |
-30°F to 150°F |
|
Air Consumption |
0.011 SCFM |
|
Operation |
Pilot operated |
|
Mounting Orientation |
Vertical or horizontal |
|
Mounting Type |
Wall mount |
|
Air Connections |
Molded backplate connections |
|
Dimensions (H x W x D) |
3-1/4" x 2" x 1-5/8" |
|
Weight |
Approximately 0.5 lbs |
|
Cover |
Sold separately |
|
Application |
Humidification and dehumidification |
Key Benefits
-
Direct-acting proportional control: Increases pneumatic output pressure as relative humidity rises.
-
15% to 75% RH scale range: Accommodates various commercial HVAC humidity control requirements.
-
Adjustable throttling range: Allows technicians to fine-tune controller sensitivity between 3% and 15% RH.
-
Pilot-operated design: Supports proportional pneumatic control of compatible equipment.
-
25 PSI maximum operating pressure: Suitable for compatible pneumatic HVAC control systems.
-
Two-pipe configuration: Supports compatible pneumatic valves and damper actuators.
-
Flexible mounting options: Accommodates vertical and horizontal wall installations.
-
Integrated air connections: Simplifies pneumatic tubing installation.
-
Low air consumption: Operates at approximately 0.011 SCFM.
-
Replacement humidity controller: Suitable for servicing existing Honeywell pneumatic building automation systems.
Common Questions
What is the Honeywell HP970A1009 pneumatic humidistat used for?
The Honeywell HP970A1009 provides proportional humidity control of compatible pneumatic valves and damper actuators in commercial air conditioning, humidification, and dehumidification systems.
What does direct acting mean on a pneumatic humidistat?
Direct acting means the pneumatic branch pressure increases as the measured relative humidity increases.
What is the difference between the Honeywell HP970A1009 and HP970B1007?
The HP970A1009 is direct acting, while the HP970B1007 is reverse acting. Both feature a humidity scale range of 15% to 75% RH and an adjustable throttling range of 3% to 15% RH.
Does the Honeywell HP970A1009 include a cover?
No. The cover is sold separately. Verify the appropriate cover model based on the mounting orientation and humidity setpoint display requirements.
Does the Honeywell HP970A1009 require an electrical power supply?
No. This humidistat operates using compressed control air rather than an electrical power supply.
Can the Honeywell HP970A1009 be mounted horizontally or vertically?
Yes. The humidistat supports both horizontal and vertical mounting configurations.
What should technicians check before replacing a pneumatic humidistat?
Technicians should verify the control action, pneumatic supply pressure, tubing configuration, actuator compatibility, humidity setpoint, and throttling range. Clean, dry control air and proper calibration are essential for accurate humidity control and reliable operation.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.