Johnson Controls T-5210-1004 Temperature Transmitter
The Johnson Controls T-5210-1004 is a precision pneumatic temperature transmitter designed for proportional sensing in demanding HVAC systems. This unit features a 3 to 15 psig output pressure range, converting sensed temperatures into a linear pneumatic signal for accurate controller input. Built with a 5-1/2 inch capillary and bulb, it provides reliable remote sensing capabilities across an operating range of 40°F to 240°F, with a maximum element temperature rating of 310°F. Operating on a 20 psig supply pressure, the T-5210-1004 maintains an efficient 45 SCIM air consumption and output flow capacity, ensuring minimal load on the compressed air plant. This model serves as the current direct replacement for the T-5220-1004, allowing for seamless mechanical integration during system retrofits or repairs. For technicians managing pneumatic control loops, this transmitter offers the ruggedness and repeatability required for industrial environmental control.
- Direct Replacement: Engineered to replace the legacy T-5220-1004 without requiring extensive recalibration or mounting modifications.
- Precise Signal Conversion: Delivers a consistent 3-15 psi pneumatic signal for high-linearity temperature tracking.
- High Flow Capacity: The 45 SCIM output flow ensures rapid response times in long-run pneumatic tubing installations.
- Durable Sensing Bulb: Features a robust capillary design capable of withstanding element temperatures up to 310 degrees Fahrenheit.
- Standard Supply Pressure: Optimized for standard 20 psi supply air, making it compatible with most existing building automation infrastructure.
Common Questions
Can the T-5210-1004 be used in steam applications?
While the unit can handle element temperatures up to 310°F, the overall operating environment for the transmitter body must remain within the 40°F to 240°F range. Always verify the process temperature does not exceed these mechanical limits.
What is the primary difference between this and the older T-5220 series?
The T-5210-1004 is the modern equivalent pneumatic transmitter, providing improved durability and updated internal components while maintaining the exact same terminal porting and pressure specifications as the discontinue T-5220-1004.
Does this unit require a specific mounting orientation?
Technicians should mount the transmitter vertically whenever possible to ensure optimal pneumatic calibration and to prevent moisture accumulation within the pilot or relay assemblies.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.
QUESTIONS & ANSWERS
Have a Question?