Schneider Electric (Erie) VS2342 Valve Body
The Schneider Electric (Erie) VS2342 Valve Body is a professional-grade, two-way zone valve designed specifically for demanding high-temperature and steam applications. This 3/4 inch inverted flare body provides a robust solution for retrofitting existing hydronic systems, featuring a 2.5 Cv flow coefficient and a quick-opening flow characteristic. Engineered for use with the Erie PopTop series, it allows for seamless actuator engagement without the need for complex tools, ensuring rapid serviceability in the field. The brass construction and BUNA N paddle provide reliable performance under pressures up to 300 psig and media temperatures up to 250°F when paired with an AH-series high-closeoff actuator. As a two-position (on/off) component, the VS2342 is essential for precise thermal management in both heating and cooling systems, maintaining an ANSI Class IV leakage rating to prevent energy loss in the closed position.
Key Benefits for Contractors:
- Inverted Flare Retrofit: Specifically designed for 3/4" inverted flare connections, making it an ideal drop-in replacement for legacy Erie zone valve bodies.
- Steam Rated Performance: Rated for low-pressure steam applications up to 15 psig, providing versatility beyond standard hot and chilled water systems.
- PopTop Compatibility: Features the industry-standard PopTop interface, allowing for one-handed actuator removal to simplify maintenance and installation.
- Reliable Closeoff: Delivers a maximum closeoff pressure of 40-50 psid (depending on the actuator used) to ensure positive shutoff and system efficiency.
Common Questions & Technical Insights:
Is the VS2342 compatible with any actuator?
This valve body is designed for use with Erie PopTop series actuators. For steam or high-temperature fluid applications, a high-performance (AH-series) actuator is required to handle the thermal load and ensure proper closeoff.
Can this valve be used for mixing or diverting?
No, the VS2342 is a two-way valve body intended for two-position (on/off) flow control. For mixing or diverting applications, a three-way body pattern from the Erie VT/VS series must be utilized.
What is the maximum pressure rating for this unit?
The valve body is rated for a maximum static pressure of 300 psig (2067 kPa), making it suitable for high-rise residential and commercial HVACR applications.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.
QUESTIONS & ANSWERS
Have a Question?
Be the first to ask a question about this.