Weil McLain 450-021-243 Draft Hood
The Weil McLain 450-021-243 Draft Hood is the vertical draft hood used on size 5 boilers in the Weil McLain CG gas family, including the CGa-5. A draft hood is a passive safety device on an atmospheric boiler, and it does more than join the appliance to the vent. The open skirt lets room air blend into the flue stream, which steadies draft at the burners. If the chimney pulls too hard, the hood draws extra dilution air. If a downdraft pushes backward, the opening gives it somewhere to go other than straight through the combustion chamber.
This hood has a crimped top collar for the vent connection, a flared conical body with an open skirt and a long inlet pipe below it that reaches down toward the boiler. The part description includes the sizing code DH-V 7D NOM x 6D NOM x 23.93, so compare those figures with your existing hood before ordering. Instructions stamped on the skirt state that the draft hood must be installed without alteration, and that the clearance between the bottom of the skirt and the top of the jacket is to be 13-3/4 inches. Treat both statements as installation requirements.
Replace a draft hood that is rusted through, crushed, perforated or no longer sitting properly on the boiler. Corrosion at the hood often points to a venting or condensation problem, so find the cause before closing up the job. Shut off the boiler and let the vent cool, support the vent connector, and lift out the old assembly. Set the new hood to the marked clearance, secure the vent joints as code requires and never cut the pipe, drill the skirt or substitute a different hood. After startup, check for spillage at the skirt with the boiler firing under normal building conditions and verify draft in the chimney.
Key Benefits
- Stable Burner Draft: The open skirt buffers the burners from chimney surges and downdrafts that can disturb the flame.
- Sized for Size 5 Boilers: 450-021-243 is the hood shown for the CGa-5, helping you avoid the neighboring sizes that look nearly identical.
- Printed Install Guidance: The skirt marking gives a required clearance of 13-3/4 inches to the jacket top, putting the key setup figure right on the part.
- Replaces Damaged Venting Parts: A sound hood removes holes and distortion that can allow flue products to escape into the boiler room.
Common Questions
- Which boiler size takes the 450-021-243 hood? It is the size 5 draft hood, shown for the CGa-5 and associated with CG family size 5 boilers. Confirm your model and series on the rating label.
- Can I shorten or modify the draft hood? No. The marking says it must be installed without alteration. Changing its dimensions can affect draft and allow flue gas spillage.
- How do I test for spillage after replacement? With the boiler firing and the house in normal operating condition, check around the skirt with a smoke source or mirror after the vent warms, and use a combustion analyzer to confirm safe operation.
Disclaimer: While we strive for 100% accuracy, product data and specifications are subject to change. Please contact our team to confirm compatibility or technical details before purchasing.